
- 13mm
- 20mm
- 25mm
- 30mm
- 40mm
- 50mm
- Dry-type water meter
Eliminates visibility problems caused by water droplets, air, etc. - Digital pointer display
Eliminates misreading of digits - Equipped with pilot
Minute flow can be checked - Easy-to-read dry-type digital display
- Output pulse rate 1m3/P
Display
Pilot allows you to check micro-flow rate
Eye-friendly display
Ergonomically designed. The numbers are clearer in dark areas and do not halate in bright areas.

Feature
Pulse transmitting water meter to meet a variety of situations.
Click to enlarge
2-wire transmitter

Operation
The reed switch of Model GD2A (2-wire transmitter) operates with the magnet built into the hot water meter as shown in the figure below.
Caution
- The pulse width (time it is ON) varies depending on the flow rate.
- If the hot water meter stops when the reed switch is in the ON state, the reed switch will remain ON as long as there is no hot water flow. Similarly, if the hot water meter stops when the reed switch is OFF, the reed switch remains OFF as long as there is no hot water flow.
- When a pulse relay model GT-ER2DM (manufactured by us) is used, the outgoing pulse of the meter can be output as a stable one-shot (approx. 0.1 second) no-voltage contact. Model GT-ER2DM is recommended for input to computers, data loggers, etc. (For details, refer to the specifications for model GT-ER2DM.) Also, when inputting directly to a central monitoring panel, data logger, etc., the input specifications of the central monitoring panel or other equipment should match the specifications of the above-mentioned transmitter unit.
External Dimensions
The 2-wire system makes wiring work very easy!
No troublesome work is required.
Click to enlarge
Wiring Method
How to wire with a pulse counter (model KDC-811/KDC-812) (for water meters with pulse transmitting function only)
Click to enlarge
Specification
Systematized Weighing Instrument Symbol
If the instrument has a pulse output function, a specific number is indicated after the R mark.
The first "26" indicates the pulse signal method, which may vary depending on the manufacturer.
The second half "13" indicates the pulse rate, which is 1,000L/P (1m3/P).
Pulse width (ON time) at maximum flow rate
- ・The ON time of the pulse varies depending on the flow rate because the reed switch is operated by a magnet.
- ・Therefore, the ON time of the pulse is shortest at the maximum flow rate, and the time is as follows
- ・Therefore, the ON time of the pulse is shortest at the maximum flow rate, and the time is as follows.
Click to enlarge
About Transmission Distance
The transmission distance when connecting the contact pulse output from the meter to the receiving instrument depends on the input specifications of the receiving instrument.
Please contact the manufacturer of the receiving instrument.
In the case of our receiving instrument
(Example) In case of connection to models KDC-811/KDC-812 → within 200m
・In case of connection to a pulse repeater model GT-ER2DM→within 3 km
Instantaneous flow rate
It is not possible to display and record the instantaneous flowrate by converting the contact pulse signal into an analog signal such as 4 to 20 mA, because the pulse unit for transmission is too large. In such cases, please use our electronic water meter.
Download catalog
Specifications, External drawing
[Tangential-flow-vane wheel type] Union connection type
![[Tangential-flow-vane wheel type] Union connection type](/asset/img/product/water/pulse/gseries01/tangent_spec.jpg)
- Specifications (PDF)
-
Model :
[Axial-flow vane wheel type] Union connection type
![[Axial-flow vane wheel type] Union connection type](/asset/img/product/water/pulse/gseries01/shaft_spec.jpg)
- Specifications (PDF)
-
Model :
